The transmitter is designed for the transformation of a thermocouple (TC) sensor signal in a fixed measuring range. The standardized output signal used for process measurement is a 4 to 20 mA signal. This means fast, easy and cost-saving temperature measuring as well as reliable and precise measured values for for a wide range of industry applications.
Fixed range temperature head transmitter for converting a TC input signal into a 4 to 20 mA analog output signal
Input: Thermocouple (TC)
장점
High accuracy in complete ambient temperature range
Failure information when sensor breaks or short circuits as per NAMUR NE 43
EMC as per NAMUR NE 21, CE
Ex approval: ATEX Ex ia and dust zone 22 in compliance with EN 50281-1; FM IS; CSA IS
By integrating a thermometer with iTHERM TwistWell thermowell with advanced helical design, operators can achieve superior steam quality and significantly reduce vortex-induced vibrations.
To meet the challenges of temperature monitoring in such critical processes, a thermowell design has been developed that responds to process changes up to five times faster than standard designs.
The Ziegler-Natta process uses hazardous chemicals like titanium tetrachloride. Precise temperature measurement is crucial to prevent runaway reactions and ensure safety and efficiency.
8...35 V DC (standard-version) 8...30 V DC (Ex-version)
Installation
Terminal head form B
Accuracy
(Type K) <= 0,5 K (Type K) <= 0,9 °F
Galvanic isolation
yes
Certification
UL Ex IS UL Ex NI GOST Ex i GL marine approval GOST Metrology GL (German Lloyd) ATEX EEx ia, Ex nA, Ex tc, Ex ia CSA IS, NI CSA General Purpose FM IS, NI FM+CSA IS, NI EAC Ex ia
Temperature head transmitter iTEMP® TMT181, TMT187, TMT188 Safety instructions for electrical apparatus certified for use in explosi on-hazardous areas (II 3D).